FIRE SAFETY IN EDUCATIONAL INSTITUTIONS— CODE OF PRACTICE

images

FOREWORD

This Indian Standard has been adopted by the Bureau of Indian Standards, after the draft finalized by the Fire Safety Sectional Committee had been approved by the Civil Engineering Division Council.

Functional need of educational building is different from other buildings. It therefore requires specific fire safety measures suited to such type of  building. The Fire Safety Sectional Committee therefore decided to formulate a separate standard on fire safety  equirements of school buildings.

The hazards of fire in educational buildings can be considerably lowered by adoption of certain pre-determined fire safety measures with regard to proper planning of  buildings, choice of proper materials and components, electrical equipment’s and making  suitable provisions for fire detection and suppression system.

The composition of the technical Committee responsible for the formulation of this standard is given at Annex A.

1 SCOPE

This code covers the fire safety requirements in educational institutions.

cfshigheredjune15

2 NORMATIVE REFERENCES

The Indian Standards listed in Annex A contain provisions which, through reference in the text, constitute provisions of this standard. At the time of publication, the editions indicated were valid. All standards are subject to revision, and parties to agreements based on this standard are encouraged to investigate the possibility of applying the most recent editions of the standards are given in Annex A.

3 CLASSIFICATION

3.1 For the purpose of the standard, the classification of educational buildings should be as given in 3.1.1.

3.1.1 All buildings shall be classified according to the use or the character of occupancy and shall be in accordance with IS 1641.

Buildings and structures under Group B shall be further subdivided as follows:

a)Subdivision B-1 schools up to higher secondary level This subdivision shall include any building or a group of  buildings under single management which is used for students not less than 20 in number.

b) Subdivision B-2 all others / training institutions This subdivision shall include any building or a group of buildings under single management which is used for students not less than 100 in number.

NOTE If residential accommodation is provided in the schools/institutions, it should be classified as building in subdivision A-3.

4 TYPES OF CONSTRUCTION

4.1 All educational buildings of permanent nature shall be of  Type I construction having external shell and load bearing elements of 4 h fire resistance rating, while internal/non load bearing walls shall have 2 h fire resistance rating. Floors shall have same fire resistance as that of external shells, and false ceiling, if any shall have rating as laid down in IS 1642. Basements, if constructed should not be used for classrooms or laboratories/libraries and  assembly halls.

4.2 All educational buildings not of permanent nature, may have constructions conforming to Type II or Type III construction as per IS 1642. All such buildings shall be restricted to ground and one upper floor only and the floor area not exceeding to 1000 m2 on each floor.

NOTE – Temporary structures such as tents or with thatched construction should not be allowed for housing educational institutions.

5 OCCUPANT LOAD

5.1 Occupant load shall be in accordance with IS 1644.

6 ARRANGEMENT OF EXIT

6.1 Exits from the upper  floor should be so located that no point in the floor is more than 22.5 m from the nearest exit, for the Type I, Type II and Type III construction.

NOTE – Type IV construction is not allowed for construction of educational buildings. 6.2 Exits should be so arranged that at least two

separate exits are available in every floor area. Exits shall be as remote from each other  as practicable and so arranged that there are no pockets or dead ends of appreciable size in which occupants may be trapped.

6.3 Every room with a capacity of 45 persons in area shall have at least two doorways.

6.4 Elevators, lifts and escalators shall not be counted as exits.

6.5 Fire escapes constitute only means of the required exit and should not be taken into account in calculating the evacuation time of the building. Fire escapes shall always be kept in sound operating conditions.

7 CORRIDOR AND PASSAGE WAYS

7.1 Exit corridors and passage ways shall be of width not less than the aggregate required width of exit doorways leading from them in the direction of travel to the exterior.

7.2 Where stairways discharge through corridors and passageways, the height of corridors and passageways shall be not less than 2.4 m.

7.3 All internal staircase, lift, lobbies and corridors should be adequately ventilated and illuminated. 

8 DOORWAYS

8.1 No exit doorway shall be less than 1 m in width except assembly halls where door width should not be less than 2 m.

8.2 The height of door shall not be less than 2 m.

8.3 These shall be opening outwardly.

8.4 Overhead or sliding door shall not be installed.

NOTE – In case of buildings where there is Central Corridor the door shall open inwards to allow smooth flow of traffic in the corridor.

8.5 These shall be open able from inside and shall not be opening immediately on flight.

9 STAIRCASE

9.1 Any building having area more than 500 m2 on each floor and 15 m or more in height shall have minimum two staircases of enclosed type; at least one of these shall be on external wall and shall directly open to exterior, interior open space or to an open place of safety. Further the provision or otherwise of alternative staircase shall be subject to the requirements of travel distance being complied with.

9.2 Internal Staircases

9.2.1 Internal stairs shall be constructed of non combustible materials throughout. Hollow combustible construction shall not be permitted.

9.2.2 Internal staircases shall be constructed as a self-contained unit with an external wall constituting at least one of its sides and shall be completely enclosed.

9.2.3 Staircase shall not be arranged round a lift shaft.

9.2.4 No gas piping shall be laid in the stairway.

9.2.5 Notwithstanding, the detailed provision for exits in the educational buildings, the width of staircase shall not be less than 1.5 m up to a height of 30 m.

NOTE – Buildings above 30 m height are not permitted.

9.2.6 Minimum width of treads shall not be less than 300 mm. The treads should be constructed and maintained in a manner to prevent slipping.

9.2.7 Maximum height of riser shall not be more than 150 mm and number shall be limited to 15 per flight.

9.2.8 Height of railing shall be more than 1 m. Gap between verticals should not exceed 200 mm. The gap should be reduced to 150 mm where small children are likely to use the staircase.

9.2.9 The number of people in between floor landings in staircase shall not be less than the population on each floor for the purpose of design of staircase. The other main parameters for the design of staircase are as given below:

a)The minimum head room in a passage under the landing of a staircase and under the staircase shall be 2.2 m.

b)For building 15 m in height or more, access to main staircase shall be through a fire smoke check door or 1 h fire resistance rating. Fire resistance rating may be reduced to half an hour for residential buildings.

c)No living space, store or other fire risk shall open directly into the staircase or staircases.

d)External exit door of staircase enclosure at ground level shall-open directly to the open spaces or through a draught lobby, if necessary.

e)The main staircase and external staircase shall be continuous from ground floor to the terrace level.

f)No electrical shafts/AC ducts or gas pipe, etc, shall pass through the staircases. Lift shall not open in staircase.

g)No combustible material shall be used for decoration/ wall panelling in the staircase. 

h)Beams/columns and other building feature shall not reduce the head room/width of the staircase.

i)The exit sign with arrow indicating the way to the escape route shall be provided at a suitable height from the floor level on the wall and shall be illuminated by electric light connected to corridor circuits. All exit way marking signs shall be flush with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipment’s. Further, all landings of floor shall have floor indicating boards prominently indicating the number of floor as per bye-laws.

The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5 x 0.5 m.

k)Individual floors shall be prominently indicated on the wall facing the staircases.

m) In case of single staircase it shall terminate at the ground floor level and the access to the basement shall be by a separate  taircase. However, the second staircase may lead to basement levels provided the same is separated at ground level by ventilated lobby with discharge points to two different ends through enclosures.

9.3 External Stairs

9.3.1 All external stairs shall be directly connected to the ground.

9.3.2 Entrance to the external staircases shall be separate and remote from the internal staircase.

9.3.3 Care shall be taken to ensure that no wall opening or window opens on to or close to a external staircase.

9.3.4 The route to the external stairs shall be free from obstructions at all times.

9.3.5 The external staircase shall be constructed of non-combustible materials, preferably of masonry and any doorway leading to it should have the required fire resistance.

9.3.6 No external staircase, used as a fire escape, should be inclined at an angle greater than 45o to the horizontal.

9.3.7 External stairs shall have straight flight not less than 1 m wide with 200 mm treads and risers not more than 190 mm. The number of risers shall be limited to 15 per flight.

9.3.8 Hand rails shall be of a height not less than 1 m and not exceeding 1.2 m.

9.4 In case the educational building has got a mixed occupancy such as auditorium, etc, necessary recommendations for exits as per the requirements as given in SP 7 : 1983 shall be followed.

10 AIR CONDITIONING

10.1 In some educational institutions, a part of it may be having air conditioning arrangement. In case of room air conditioning, no extra precautions than laid down are required. In cases, like auditorium and laboratories having central air conditioning system, the measures as laid down in IS 1642 should apply.

11 CHIMNEYS

11.1 Where chimneys are used, the requirements shall be as laid down in IS 1642 and IS 1649.

12 RESTRICTION OF SPREAD OF FIRE AND

SMOKE

12.1 The vertical shafts/ducts meant for electrical wiring, drainage pipes, etc, shall be effectively sealed at  all floor levels and shall be enclosed by 2 h fire resistance enclosures. Wherever inspection doors are required, these shall be of not less than 1 h fire resistance.

12.2 The material chosen for other use shall be as far as non-combustible and the wood/other material shall be treated with fire retardant composition if its use is unavoidable.

12.3 The laboratories which are likely to have highly flammable material/chemicals, etc, should be located in separate block and adequate precautions shall be taken to have separate stores for keeping hazardous chemicals.

12.4 The adequate care shall be taken while using any gas for burners, etc, in laboratory/kitchens and necessary precaution shall be taken for storage of gas in form of bullet, tanks, battery or cylinders, etc, as per rules.

13 ELECTRICAL EQUIPMENT AND SAFETY RULES

13.1 Transformer building/HT and LT control panels having aggregate oil capacity greater than 2 000 litres shall be housed in separate rooms/enclosures 6 m away, properly fenced.

13.2 Staircases and corridors lighting shall have separate circuits.

13.3 Miniature Circuit Breakers/Earth Leakage Circuit Breakers shall be provided in the circuits.

13.4 Earth connection shall be provided in building which are 15 m or more in height.

13.5 The lighting protection system for the buildings shall generally conform to IS 2309.

14 FIRE SAFETY MEASURES

14.1 The requirements of wet riser, down comer installations and capacity of water storage tanks and fire pumps should be as given below:

a) For buildings less than 15 m in height:

Installations                      Minimum Requirements

 

Hose reel                            To be provided (For more

                                           than 2 storeyed buildings

                                           and covered area exceeding

                                           1 000m2)

Wet riser                            –

Down comer                      To be provided

Yard hydrant                      –

Automatic                           To be provided (In case of the

sprinkler system                  buildings having basement

                                          area 200 m2 and more)

Manually                            –

operated

electric fire

alarm system

Installations                    Minimum Requirements

Automatic                         

detection and

alarm system

Underground                     50 000 1 (If total covered

static water                        area exceeds 1500 m2)

storage tank

Terrace tank                      10 000 1 (In case of hose

                                          reel and 20 000 1 in case the

                                          buildings having basement

                                          area 200 m2 and more

Near under-                      One electric pump and one

ground  static                    diesel pump of capacity

tank, (fire pump                1620 1/min and one electric

with) minimum                  pump of capacity 180 1/min

pressure of 0.3

N/mm2 at

terrace level

Pump at terrace                  4501/min, in case of hose reel

level with                           (900 1/min in case of hose

minimum                            reel and in case the

pressure of 0.3                    buildings having basement

N/mm2                                          area 200 m2 and more)

b) 15 m and above but not exceeding 30 m in height

Installation                        Minimum Requirements

Hose reel                              To be provided

Wet riser                               To be provided

Down comer                         To be provided

Yard hydrant                         To be provided

Automatic                             To be provided (In case the

sprinkler system                    building is having a basement

                                            area 200 m2 and more)

 Manually                              To be provided

operated

electric fire

alarm system

Automatic                             Not to be provided

detection and

alarm system

Under ground                      10 000 1 for every 100 m2

static water                         with a minimum of 5 000 1

storage tank                        up to maximum of 1 00 000 1

Terrace tank                        20 000 1 (30 000 1 in case of

                                          the buildings having basement

                                            area 200 m2 and more)

Near under-                           One electric and one diesel

Ground static                        pump of capacity 2 850

tank, fire pump                     1/min and one electrical

with minimum                      pump of capacity 180 1/min)

pressure of 0.3

N/mm2 at terrace

level

Pump at terrace                     900 1/min (1 620 1/mm in

level with mini-                     case the buildings having

mum pressure of                   basement area 200 m2 and

0.3 N/mm2                                     more)

 

14.2 Fire Detection and Alarm System

If automatic fire detection and alarm system is employed, the installation shall conform to IS 2189. The detectors, if provided, shall conform to IS 2175 and IS 11360.

14.3 First aid fire fighting appliances shall be provided and installed and maintained in accordance with IS 2190.

15 EMERGENCY AND ESCAPE LIGHTING

15.1 Emergency lighting shall be powered from a source independent of that supplying normal lighting.

15.2 The emergency lighting shall be provided to be put on within 5 second (preferably within 1 second) of the failure of the normal lighting supply.

15.3 Emergency lighting luminaries and their fittings shall be non-flammable.

15.4  It is essential that the wiring and installations of the emergency lighting systems are of high quality so as to ensure their perfect serviceability at all times.

15.5 The emergency lighting system shall be capable of continuous operation for a minimum duration of 1 h 30 min even for smallest premises.

15.6 It shall be ensured that the emergency lighting system is well maintained by periodical inspections and tests so as to ensure their perfect serviceability at all times.

15.7 Escape lighting shall be capable of:

a) Indicating clearly and unambiguously the escape routes,

b) Providing adequate illumination along such routes to allow safe movement  of persons towards and through exit, and

c) Ensuring that fire alarm call point and fire fighting equipment’s provided along the escape routes can be readily located.

15.8 Escape lighting luminaries shall be sited to cover the following locations: a) Near each intersection of corridors,

b)At each exit door,

c)Near each change of direction in the escape route,

d)Near each staircases so that each flight of stair receives direct light,

e)Near any other change of floor level,

f)Outside each final exit and close to it,

g)Near each fire alarm call point,

h)Near fire-fighting equipment, and

j)To illuminate exit and safety signs as required by the enforcing authority.

NOTE – For the purpose of this clause ‘near’ is normally considered to be within 2 m measured horizontally.

ANNEX A

(Clause 2)

LIST OF REFERRED INDIAN STANDARDS

 

IS No.                                     Title

1641: 1988                     Code of practice for fire safety of         

                                       buildings (general): General

                                       principles of fire grading and classification

                                   (first revision)

1642 : 1989                    Code of practice for fire safety of

                                        buildings (general): Details of

                                        construction (first revision)

1644 : 1988                     Code of practice for fire safety of

                                        buildings (general): Exit requirements

                                        and personal hazard (first revision)

1649 : 1962                     Code of practice for design and

                                        construction of flues chimneys for

                                        domestic heating appliances (first

                                        revision)

2175 : 1988                     Specification for heat sensitive

                                        fire detectors for use in automatic

                                        fire alarm system (second revision)

2189 : 1988                     Code of practice for selection, installation

                                        spallation and maintenance of

                                        automatic fire detection and

                                        alarm system (second revision)

2190 : 1992                    Code of practice for selection, installation

                                       Spallation  and maintenance of

                                       portable first-aid fire extinguishers

                                       (third revision)

2309 : 1989                    Code of practice for the protection

                                       of buildings and allied structures

                                       against lighting (second revision)

11360 : 1985                  Specification for smoke detectors

                                       for use in automatic electrical fire

                                       alarm system

SP 7 : 1983                     National building code of India:

                                       Part IV Fire protection

 

Chairman                                                             Representing

 

SHRI J.N . VAKIL                                                   Tariff Advisory Committee, Mumbai

Members

SHRI K. RAVI (Alternate to

Shri J. N. Vakil)

DR.A.K.BHALLA                                                      Ministry of  Defense (CEESO), New Delhi            

DR. K. S.UPPAL (Alternate)

SHRI. S. N. CHAKRABORTY                                   Tariff Advisory Committee, Chennai,                

                                                                               Calcutta

SHRI P.K. MAJUMDAR (Alternate)

CHIEF FIRE OFFICER (Alternate)                              Municipal Corporation of           

                                                                                 Mumbai (Mumbai Fire Brigade),  Mumbai

SHRI R.N. CHACHRA                                                 Metallurgical and Engineering Consultants (India) Ltd, Ranchi

SHRI S.M.DESAI                                                        In personal capacity (B-4/5 A. G. Khan Road, Municipal Officers Society,

                                                                                 Worli, Mumbai)

SHRI RAMESH DHOBLEY                                           Bhabha Atomic Research Centre, Mumbai

SHRI S.K.DHERI                                                         Delhi Fire Service, Government of  Delhi, New Delhi

SHRI R.C.SHARMA (Alternate)

FIRE ADVISORY                                                          Ministry of  Home Affairs, New Delhi

DY FIRE ADVISOR (Alternate)

SHRI J.S.GAHLAUT                                                      State Bank of India, Mumbai

SHRI P.N.GHOSH                                                          In personal capacity (J-191 6, Chittaranjan Park, New Delhi 110019)

SHRI C.P.GOSAIN                                                         Central Public Works Department, New Delhi

SHRI S.C.GUPTA                                                          Lloyd Insulations (India) Pvt Ltd, New Delhi

SHRI SANJEEV ANGRA (Alternate)

SHRI M. M. KAPOOR                                                    Engineers India Ltd, New Delhi

SHRI RANA PRATAP (Alternate)

SHRI A.R. KHAN                                                          Bharat Heavy Electricals Ltd, Bhopal

SHRI NATARAJAN (Alternate)

SHRI G.B. MENON                                                       In personal capacity (A-5, Puzhakkara Padam, Vennala, Cochin)

MEMBER(HYDRO-CONSIRUCTION MONITORING)       Central Electricity Authority, New Delhi

CHIEF ENGINEER(HTD-II) (Alternate)

MANAGING DIRECTOR                                                Loss Prevention Association of India Ltd, Mumbai

SHRI T.V . MADHUMANI (Alternate)

SHRI V. B. NIKAM                                                       In personal capacity (4/34, Haji Ali Municipal Officers Cooperative Housing                                                                                   Society, Mumbai)

SHRI D.PADANABHA                                                  Tata Consulting Engineers, Mumbai

SHRI B.S. VENKATESH (Alternate)

SHRI P.N. PANCHAL                                                   In personal capacity (46, Block E-I, Pocket-II, Sector 15, Rohini, Delhi)

RETIRED DY INSPECTOR GENERAL(FIRE)

CISF (Alternate)

PRESIDENT                                                               Institution of  Fire Engineers (India), New Delhi

SECRETARY (Alternate)

SHRI V.M. RANALKAR                                               Ministry of Petroleum and Natural Gas

SHRI K.P.SHARMA                                                    Ministry of Railways, New Delhi

ASSTT SECURITY COMMISSIONER (Alternate)

SHRI S. K. SHANGARI                                               Engineer-in-Chief’s Branch, New Delhi

LT-COL A.T.PARNAIK(Alternate)

DR T.P.SHARMA                                                        Central Building Research Institute, Roorkee

DR GOPAL KRISHNAN (Alternate)

SHRI R.SUNDARAJAN                                              National Thermal Power Corporation Ltd, New Delhi

SHRI S.K.CHATTOPADHAYAY(Alternate)

SHRI M.S. TYAGI                                                    Ministry of  Labour (Regional Labour Institute, Kanpur), New Delhi

SHRI P. K. SAKSENA (Alternate)

SHRI K.K.SHARMA,                                                Director General, BIS (EXofficio Member)

Director (Civil Eng.)

                                                                           Member Secretary

                                                                          S. CHATURVEDI

                                                                         DY DIRECTOR (CIV ENGG), BIS

Bureau of Indian Standards

BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote harmonious development of the activities of standardization, marking and quality certification of goods and attending to connected matters in the country.

Copyright

BIS has the copyright of all its publications. No part of these publications may be reproduced in any form without the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing the standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to copyright be addressed to the Director (Publication), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of ‘BIS Handbook’ and ‘Standards Monthly Additions’.

This Indian Standard has been developed from Doc: No. CED 36 ( 5210).

 

Amendments Issued Since Publication


Amend No.                                               Date of Issue                                                                              Text Affected


BUREAU OF INDIAN STANDARDS

Headquarters:

Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002                          Telegrams: Manaksanstha

Telephones: 323 0131,323 33 75,323 94 02                                                           (Common to all offices)                                                                                       

Regional Offices:                                                                                                                  Telephone

Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg                                              323 76 17,323 38 41

             NEW DELHI 110002

Eastern : l/14 C.I.T. Scheme VII M, V.I.P. Road, Maniktola                                     337 84 99,337 85 61

              CALCUTTA 700054                                                                                337 86 26,337 9120

                    

Northern : SCO 335-336, Sector 34-A, CHANDIGARH 160022                                                60 38 43

                                                                                                                                         60 20 25

Southern : C.I.T. Campus, IV Cross Road, CHENNAI 600113                                 235 02 16,235 0442

                                                                                                                        235 15 19,235 23 15

Western : Manakalaya, E9 MIDC, Marol, Andheri (East)                                      832 92 95,832 78 58

               MUMBAI 400093                                                                               832 78 91,832 78 92

Branches : AHMADABAD. BANGALORE. BHOPAL. BHUBANESHWAR.

                  COIMBATORE. FARIDABAD. GHAZIABAD. GUWAHATI.

                  HYDERABAD. JAIPUR. KANPUR. LUCKNOW. NAGPUR.

                  PATNA. PUNE. THIRUVANANTHAPURAM.