Passive Fire Protection Essential on Steel-Beam Decks for Offshore Installations

Passive fire protection (PFP) is widely used in the oil and gas industry as a method to avoid or delay collapse of offshore installations. This paper discusses the thermal and structural response observed on typical three-sided PFP beams used in the industry. Several heat-transfer finite element analyses (FEA) were performed on a range of rolled I sections and plate girders. The results provide an understanding of the influence of conduction, convection, and radiation in the heat-up mechanism of the beams.

Introduction

Many steel beams in oil and gas installations are normally coated with three-sided fire protection. Structural steel I sections are often the main structural sections used to support the flooring of the various decks present within a module on an offshore platform. The flooring is commonly in the form of steel grating; additionally, beams supporting pipe runs are also commonly left unprotected above the top flange. The top flange of the structural steel I sections cannot be easily coated with PFP because this would prove impractical and expensive. However, there could be a severe disadvantage in use of this form of protection. In the event that the member is engulfed in fire, the top flange is completely unprotected and exposed to flame. This will allow free conduction of heat through the beam cross section. The strength of the structural section will then decrease with increasing temperature. A nonuniform temperature distribution will be developed through the cross section of the member and will reduce its load-carrying capacity.

Current design codes do not present economic methods to compute the lateral torsional buckling resistance of members coated with three-sided protection because of the development of a nonuniform temperature distribution when the beam is engulfed in fire. This presentation aims to highlight the implications of the use of three-sided protection on structural members, and provides some solutions that can be explored during the detail design of PFP.

Three-Sided PFP

Deck members that have plating or grating on their top flange will generally have three-sided PFP applied (i.e., the surface of the top flange is left unprotected because of application/maintenance difficulties). Members below a deck plate normally require a PFP coatback applied to the underside of the deck plate, which limits the amount of thermal conduction along the deck plate and into the top flange of the section for fires from below. The section is still somewhat vulnerable to fires from above. Members below grating are vulnerable to fires from above and below.

Fig. 1 shows a schematic of different types of member PFP applications. Members without any obstructions (e.g., some columns and vertical and horizontal braces) are normally have PFP applied on all sides of the member.

Fig. 1-Schematic of different types of PFP application.

Thermal Response of I Sections With Three-Sided Fire Protection. Steel I sections that support the decks of various modules in an offshore platform are often coated with three-sided fire protection. It is often difficult to coat steel I sections on all sides because the deck often prevents application of PFP to the top flange of the I section. For example, the I sections may support a grated steel deck, which makes the application of the PFP to the top surface of these members impractical and expensive. In the event that the member is engulfed in fire, the top flange is completely unprotected and exposed to flame.

The unprotected surface of the top flange causes a rapid heat-up of the top flange if exposed to fire. Thermal conduction then heats up the web of the section; a nonuniform temperature distribution will then develop through the section (Fig. 2). This nonuniform temperature distribution will reduce the load-carrying capacity of the member.

Fig. 2-Nonuniform temperature distribution caused by three-sided fire protection.

Heat Transfer Affecting the Thermal Response of Three-Sided PFP Beams. The heat conduction on the three-sided protected beam is driven by the temperature differences, which are attributed to (1) radiant and convective heat up through the PFP and (2) heat conduction from the unprotected top flange. The top flange will reach the fire temperature much faster than bottom flange. The smaller the section depth, the higher the temperatures that are reached at the bottom flange.

The average temperature of the cross section will depend on the depth of the I beam as well as the duration of the fire scenario. To assess the influence of these two variables, a series of sensitivity heat-transfer analyses was performed, assessing the effect of the depth of the beams by modeling three different depths.

The first result that can be observed is for the case when only conduction from the top flange was considered as the heating mechanism. It is observed that conduction is a slow heat-transfer mechanism and seems to be independent of the thickness of the web’s plate. The two primary variables affecting the average temperature in the cross section of the beam are depth and the duration of the fire; smaller beam depths will have larger average cross section temperatures for a given time. Similarly, the longer the duration of the fire, the larger the average temperatures are increased because of the conduction from the top flange toward the bottom flange.

When radiation through the PFP is considered, it can be observed that the temperatures on the beam’s cross section increased faster than when only conduction from the top is considered. Therefore, it can be concluded that the insulation provided by the PFP also plays a part in controlling the average temperature on the beam.

Mechanical Response of Three-Sided PFP Beams. The following steps summarize the mechanical effects induced by the thermal gradients that are created because of partial PFP protection in the cross section of a beam section.

Leaving the top surface of the top flange unprotected produces a thermal gradient along the cross section of the beam.

The thermal gradient produces bowing toward the hot side. Structural beams tend to be much stiffer in the in-plane than in the out-of-plane direction; therefore, vertical deformation is restrained. If lateral direction is unrestrained, lateral deformation will occur.

The concentration of compression forces at the top flange may lead to lateral buckling of the beam; the cross section will also twist in torsion, resulting in a failure mode known as lateral-torsional buckling.

Effects on Load-Carrying Capability. Load-carrying capability of three-sided PFP beams depends mainly on three criteria: lateral stability, bending strength, and shear strength. In general, beams with long spans and no lateral stiffening are more likely to fail because of lateral stability, whereas restrained beams or deep sections are more likely to fail by bending strength failure.

Editor’s Note

Strengthening Fire & Safety Awareness as We Approach 2025 As we stand just an inch away from the new year 2025, the urgency for increased...

Parcel tracking: hours reduced to seconds with integrated, visualized solutions

A bustling warehouse, filled with endless rows of shelves and stacks of boxes, is now common, especially during big promotions. But as the global...

Related Article

Editor’s Note

Strengthening Fire & Safety Awareness as We Approach 2025 As we stand just an inch away from the new year 2025, the urgency for increased...

Parcel tracking: hours reduced to seconds with integrated, visualized solutions

A bustling warehouse, filled with endless rows of shelves and stacks of boxes, is now common, especially during big promotions. But as the global...

Sparsh CCTV and Cron AI Forge Partnership for the Autonomous Future

Transforming Video Surveillance, Intelligent Transportation Systems (ITS), and Infrastructure Automation New Delhi, Nov 4, 2024 – Sparsh CCTV, a leader in innovative security solutions, and...

Smart Learning Imperative through Skill Development and Training to Leverage Security Market Opportunities

Learning how to learn is life's most important skill, thus skill development and training continues to be an integral part of any successful security...

Healthcare Security Challenges Need a Smart Prescription

The Healthcare Security is again back in the focus due to various security incidents in the hospital premises across India. The burgeoning healthcare infrastructure...