Our 5 Monthly Magazines

TRENDING NOW

The only Fire Safety Security Dedicated Publication House publishing 5 monthly magazines on Fire & Safety, Occupational Workmen Safety and Industrial Safety, Security and Surveillance including Cyber Security Since 1998

Our Clients

HomeArticle/ FeaturesPassive Fire Protection Essential on Steel-Beam Decks for Offshore Installations

Passive Fire Protection Essential on Steel-Beam Decks for Offshore Installations

Passive fire protection (PFP) is widely used in the oil and gas industry as a method to avoid or delay collapse of offshore installations. This paper discusses the thermal and structural response observed on typical three-sided PFP beams used in the industry. Several heat-transfer finite element analyses (FEA) were performed on a range of rolled I sections and plate girders. The results provide an understanding of the influence of conduction, convection, and radiation in the heat-up mechanism of the beams.

Introduction

Many steel beams in oil and gas installations are normally coated with three-sided fire protection. Structural steel I sections are often the main structural sections used to support the flooring of the various decks present within a module on an offshore platform. The flooring is commonly in the form of steel grating; additionally, beams supporting pipe runs are also commonly left unprotected above the top flange. The top flange of the structural steel I sections cannot be easily coated with PFP because this would prove impractical and expensive. However, there could be a severe disadvantage in use of this form of protection. In the event that the member is engulfed in fire, the top flange is completely unprotected and exposed to flame. This will allow free conduction of heat through the beam cross section. The strength of the structural section will then decrease with increasing temperature. A nonuniform temperature distribution will be developed through the cross section of the member and will reduce its load-carrying capacity.

Current design codes do not present economic methods to compute the lateral torsional buckling resistance of members coated with three-sided protection because of the development of a nonuniform temperature distribution when the beam is engulfed in fire. This presentation aims to highlight the implications of the use of three-sided protection on structural members, and provides some solutions that can be explored during the detail design of PFP.

Three-Sided PFP

Deck members that have plating or grating on their top flange will generally have three-sided PFP applied (i.e., the surface of the top flange is left unprotected because of application/maintenance difficulties). Members below a deck plate normally require a PFP coatback applied to the underside of the deck plate, which limits the amount of thermal conduction along the deck plate and into the top flange of the section for fires from below. The section is still somewhat vulnerable to fires from above. Members below grating are vulnerable to fires from above and below.

Fig. 1 shows a schematic of different types of member PFP applications. Members without any obstructions (e.g., some columns and vertical and horizontal braces) are normally have PFP applied on all sides of the member.

Fig. 1-Schematic of different types of PFP application.

Thermal Response of I Sections With Three-Sided Fire Protection. Steel I sections that support the decks of various modules in an offshore platform are often coated with three-sided fire protection. It is often difficult to coat steel I sections on all sides because the deck often prevents application of PFP to the top flange of the I section. For example, the I sections may support a grated steel deck, which makes the application of the PFP to the top surface of these members impractical and expensive. In the event that the member is engulfed in fire, the top flange is completely unprotected and exposed to flame.

The unprotected surface of the top flange causes a rapid heat-up of the top flange if exposed to fire. Thermal conduction then heats up the web of the section; a nonuniform temperature distribution will then develop through the section (Fig. 2). This nonuniform temperature distribution will reduce the load-carrying capacity of the member.

Fig. 2-Nonuniform temperature distribution caused by three-sided fire protection.

Heat Transfer Affecting the Thermal Response of Three-Sided PFP Beams. The heat conduction on the three-sided protected beam is driven by the temperature differences, which are attributed to (1) radiant and convective heat up through the PFP and (2) heat conduction from the unprotected top flange. The top flange will reach the fire temperature much faster than bottom flange. The smaller the section depth, the higher the temperatures that are reached at the bottom flange.

The average temperature of the cross section will depend on the depth of the I beam as well as the duration of the fire scenario. To assess the influence of these two variables, a series of sensitivity heat-transfer analyses was performed, assessing the effect of the depth of the beams by modeling three different depths.

The first result that can be observed is for the case when only conduction from the top flange was considered as the heating mechanism. It is observed that conduction is a slow heat-transfer mechanism and seems to be independent of the thickness of the web’s plate. The two primary variables affecting the average temperature in the cross section of the beam are depth and the duration of the fire; smaller beam depths will have larger average cross section temperatures for a given time. Similarly, the longer the duration of the fire, the larger the average temperatures are increased because of the conduction from the top flange toward the bottom flange.

When radiation through the PFP is considered, it can be observed that the temperatures on the beam’s cross section increased faster than when only conduction from the top is considered. Therefore, it can be concluded that the insulation provided by the PFP also plays a part in controlling the average temperature on the beam.

Mechanical Response of Three-Sided PFP Beams. The following steps summarize the mechanical effects induced by the thermal gradients that are created because of partial PFP protection in the cross section of a beam section.

Leaving the top surface of the top flange unprotected produces a thermal gradient along the cross section of the beam.

The thermal gradient produces bowing toward the hot side. Structural beams tend to be much stiffer in the in-plane than in the out-of-plane direction; therefore, vertical deformation is restrained. If lateral direction is unrestrained, lateral deformation will occur.

The concentration of compression forces at the top flange may lead to lateral buckling of the beam; the cross section will also twist in torsion, resulting in a failure mode known as lateral-torsional buckling.

Effects on Load-Carrying Capability. Load-carrying capability of three-sided PFP beams depends mainly on three criteria: lateral stability, bending strength, and shear strength. In general, beams with long spans and no lateral stiffening are more likely to fail because of lateral stability, whereas restrained beams or deep sections are more likely to fail by bending strength failure.

Editors Note: A Year of Transformative Leadership in Security & Fire Safety Publications

As 2024 draws to a close, Fire & Safety reflects on a year defined by relentless innovation in advertising, branding, and promotion. Our dedication...

Safeguarding Lives: A New Era of Fire Safety and Recognition in India

On November 28, 2024, Bhubaneswar witnessed a landmark event at Hotel Hindustan International—the 65th Safe India Hero Plus Awards and the curtain raiser for...

Related Article

Editors Note: A Year of Transformative Leadership in Security & Fire Safety Publications

As 2024 draws to a close, Fire & Safety reflects on a year defined by relentless innovation in advertising, branding, and promotion. Our dedication...

Safeguarding Lives: A New Era of Fire Safety and Recognition in India

On November 28, 2024, Bhubaneswar witnessed a landmark event at Hotel Hindustan International—the 65th Safe India Hero Plus Awards and the curtain raiser for...

The essential tech needed to protect oil platforms, workers, and the environment

Oil platforms operate in one of the most high-risk environments where security and environmental risks are ever-present. To mitigate these risks, cutting-edge security technologies...

Interface with Mr. Gaurav Taywade (Director, India Operations, Vicon Industries)

Q.1. Could you brief our readers about yourself and VIcon? What's the success mantra of this wonderful journey with Vicon? About Myself and Vicon:...

‘IFSEC India is a pioneer in its domain and the biggest electronics security expo held in South Asia since 2007’

Q: The 17th edition of IFSEC India Expo is scheduled to be held from Dec 12-14 2024 in Halls 8,9,10,11 and 12 at ITPO,...